INSTALLATION MANUAL
BASIC INSTALLATION
RACK-MOUNTED EMERGENCY PA SYSTEM
MODEL NUMBERS : FS-971
FS-972
FS-973
FS-970 SERIES
Installation Precautions (For Sales Shops and Installers)
• When inspecting the speaker line insulation, disconnect the speaker lines from the PA system.
If the system's fire alarm (EL) and fire confirmation signal (EF) terminals are connected during a
dielectric strength test of the relay contact of a fire alarm system or other external systems, this
can cause damage to the PA system.
Page view 0
1 2 3 4 5 6 ... 55 56

Summary of Contents

Page 1 - FS-970 SERIES

INSTALLATION MANUAL BASIC INSTALLATIONRACK-MOUNTED EMERGENCY PA SYSTEMMODEL NUMBERS : FS-971 FS-972FS-973FS-970 SERIESInstallation Precautions (For Sa

Page 2 - TABLE OF CONTENTS

10End"Basic Installation Manual"you are reading nowSeparate book"Writing"• Finish construction work explained in the separate book

Page 3

116. EQUIPMENT RACK ASSEMBLY AND INSTALLATION6.1. Poor Installation LocationsAvoid installing the rack in the following locations.• Locations that may

Page 4 - 1. SAFETY PRECAUTIONS

126.3. Rack InstallationThe emergency rack system must be installed as shown in the figure below.Wall surface, etc. Over 0.6 m Over 2 m FrontSpace for

Page 5

136.5. Securing the Rack CR-412-6 to the FloorFour anchor bolt mounting holes (ø15 mm) are provided in the rack bottom surface to secure the rack to t

Page 6 - 2. SUPPLIED MANUALS

146.7. Rack Suspension using EyeboltsEyebolts for suspension can be mounted to the rack top panel.• Purchase the following parts separately in the mar

Page 7 - 3.1. System Summary

157. BEFORE MOUNTING THE COMPONENTS IN THE RACK7.1. Integrated Control Panel EP-0510• Chime Switch InstallationTo activate the external chime device o

Page 8

16Screw (M3x6) Chime Unit CK-0257.2. Pre-amplifier Panel PP-025B• Chime Unit (CK-025) InstallationNote: Install the Chime Unit in the Pre-amplifier Pa

Page 9 - 4. NI-CD BATTERY REPLACEMENT

174. Connect one end of the connector cable supplied with the Chime Unit to the Chime Unit' s connector, andthe other end to connector CN17 on th

Page 10 - 5. INSTALLATION PROCEDURES

188. COMPONENT INSTALLATIONThis section describes the points of installation you need to bear in mind when mounting the following maincomponents in th

Page 11 - 6.2. Rack Assembly

198.3. Emergency Power Supply PanelYou need to mount the perforated panel (PF-013B, etc.) above and below each Emergency Power SupplyPanel DS-029B. Ho

Page 12 - 6.3. Rack Installation

21. SAFETY PRECAUTIONS...42. SUPPLIED MANUAL

Page 13

208.5. Power Amplifier Panel Mounting Position• You need to mount the perforated panel (PF-013B, etc.) above and below each power amplifier panel.Howe

Page 14 - 6.9. Grounding

Supplied Connection CablesPower cord, parallel vinyl covered cable, dual phone plug balanced cableDual phone plug balanced cableDual phone plug balanc

Page 15

229.2. Pre-amplifier Panel PP-025B Connection• You can install the Chime Unit in the Pre-amplifier Panel. (Refer to p. 16.)• Input 1-A jack is located

Page 16

239.3. Power Amplifier Panel Connection• Use the same output line voltage when connecting power amplifier panels for parallel operation. You canconnec

Page 17

249.4. Emergency Power Supply Panel DS-029B Connection9.4.1. Battery connectionInternal Ni-Cd batteries are optional. Depending upon the output and nu

Page 18 - 8. COMPONENT INSTALLATION

259.4.3. About the operation of the Emergency Power Supply Panel DS-029BWhen the AC power is supplied and the Emergency Activation terminal is not sho

Page 19 - 8.4. DC Power Supply Panel

26When the emergency function is operated while the AC power is cut off (power failure)...Current flows in Coil F in the Junction Panel JP-0410 and c

Page 20

279.4.4. ConnectionsConnections of the Emergency Power Supply Panel DS-029B are classified into four methods a, b, c, and ddepending on the compositio

Page 21 - FS-971-36NA

28Connection method b for the DS-029BIn this method, two batteries (one DS-029B unit) are connected to supply power to the operation/controlsections a

Page 22

29Connection method c for the DS-029BIn this method, three or more batteries (multiple DS-029B connection) are connected to supply power to theoperati

Page 23 - JP-0410 rear panel

39. RACK INTER-PANEL CONNECTION9.1. FS-971 System Panel Connection Diagram ...

Page 24 - CHARGE CURRENT

30Connection method d for the DS-029BIn this method, three or more batteries (multiple DS-029B connection) are connected. A single DS-029B unitcontain

Page 25 - AC power

319.4.5. Connecting a single emergency power supply panel to power amplifiersThe figure below shows the method of connecting the Emergency Power Suppl

Page 26

329.5. Junction Panel JP-0410 Connection9.5.1. Connecting the Junction Panel's rear-mounted terminal block1. 24V IN/OUT terminals• The power capa

Page 27

Power Consumption303 W572 W700 W339.5.2. Connecting the AC power supply of the Junction Panel JP-0410• The Junction Panel JP-0410 supplies the AC powe

Page 28

349.6. DC Power Supply Panel Connection9.6.1. When the DC power supply panel is not required (i.e. when you can do with the junction panel'sinter

Page 29

359.6.2. When expanding the power supply for external equipmentLet us assume that one expansion power supply is added to the system solely to cover th

Page 30

369.6.4. Connection between DC power supply panel and Expansion Operation Panel EP-029Make connections using the optional expansion power cable YR-931

Page 31

379.6.5. Connection between DC power supply panel and Expansion Junction Panel JP-039Use the optional expansion power cable YR-931 for connection. Not

Page 32

3810. SETTING OF THE INTEGRATED CONTROL PANEL EP-0510Use switches SW1-SW4 on the EP-0510's control circuit board for setting. SW1SW2 SW3 SW4ON ON

Page 33

39• Evacuation Announcement interval (SW4-4 through SW4-8)Time intervals can be set for 30 seconds to 15 minutes 30 seconds in 30 seconds units.• All-

Page 34

4When Installing the Unit• Do not expose the unit to rain or an environmentwhere it may be splashed by water or other liquids,as doing so may result i

Page 35 - 24 VDC OUT 24 VDC IN

40Set equipment that can initiate Main Rack BGM. Both switches are set to OFF at the factory so as to allow theMain Rack BGM to be played from the [Ma

Page 36

0123456789ABCDEF Address switch(Address setting to 1)Expansion Junction PanelJP-039-10Expansion Junction PanelJP-039-204110FEDCBA98765432Address switc

Page 37

4212. CONNECTING THE RACK-MOUNTED COMPONENTS TO EXTERNALLINES12.1. Names of the Front-Mounted Terminal of the Junction Panel JP-041012.2. AC Power Sup

Page 38 - ON ON ON

Total speaker line wattageUnder 24 W25-40 W41-80 W81-120 W121-160 W161-200 W4312.3. Speaker ConnectionsConnect speaker cables to terminals R,N, and C,

Page 39

4412.4. Connections to the Automatic Fire Alarm SystemsBy connecting the emergency PA system to an automatic fire alarm system, voice alarms can beaut

Page 40 - Return the test switch to OFF

4513. CONNECTION INSPECTION13.1. Inspection of Connections and Wiring• After all connections are completed, inspect the connections and wiring again b

Page 41

4613.3. Speaker Line Adjustment and Measurement13.3.1. Speaker line impedance measurement (using impedance meter)Measure the impedance of each speaker

Page 42 - JP-0410 (H version)

4713.3.2. Speaker line insulation resistance measurement (Measuring instrument: Megger)Measure between the ground and the cable for each line. Do not

Page 43 - 12.3. Speaker Connections

4813.4. Speaker Sound Pressure Level Measurement[Measuring instrument: Sound level meter (A weighting network characteristics)]Measure the output soun

Page 44 - JP-0410 front panel

24 VDC0.6 AComposite audio signal tone (1st signal, 2nd signal, Warning Announcement,Evacuation Announcement, False Alarm Announcement)1st basement -

Page 45 - 13. CONNECTION INSPECTION

5When Installing the Unit• Never plug in nor remove the power supply plugwith wet hands, as doing so may cause electricshock.• Do not block the upper

Page 46

220 VAC, 50/60 Hz95 W (120 VA)10 lines each of R (Attenuator-free), N (Normal), and C (Common), M3.5 screw terminal (Maximum connectable wattage per l

Page 47

5124 V IN, M4 screw terminal24 V OUT, M4 screw terminalEmergency DS activation output: 24 VDC, 0.1 A, M4 screw terminalEmergency DS control input: 24

Page 48 - 14. POWER-ON AND INSPECTION

110 VAC, 50/60 Hz95 W (120 VA)10 lines each of R (Attenuator-free), N (Normal), and C (Common), M3.5 screw terminal (Maximum connectable wattage per l

Page 49

24 VDC650 mA [400 mA]20 lines [10 lines] each of R (Attenuator-free), N (Normal), and C (Common), M3.5 screw terminal (Maximum connectable wattage per

Page 50

24 VDCLess than 200 mAInput 1-A: –2 dBV/–62 dBV (changeable), 600 Ω, balanced, phone jackInput 1-B: –2 dBV, 600 Ω, balanced, phone jackInput 2-A: –2 d

Page 51

110/120/220/240 VAC (changeable), 50/60 Hz24 W (30 VA)Sealed Ni-Cd battery, up to 2 batteries are usable.NDC-2435 (3500 mAH/5 HR), optionalNDC-2460 (6

Page 52

Printed in Japan133-12-580-3D

Page 53

62. SUPPLIED MANUALSThe following manuals are supplied with the emergency PA system.Emergency PA System FS-970 SeriesInstallation ManualEmergency PA S

Page 54 - • Pre-amplifier Panel PP-025B

73. BEFORE STARTING INSTALLATION3.1. System Summary• The FS-971 and FS-973 permit system expansion of up to 330 lines and up to 330 emergency zones.•

Page 55

83.2. About the Emergency Power Supply3.2.1. Selection of the emergency power supply panel and batteryThe emergency PA system is designed to operate o

Page 56 - 133-12-580-3D

933027022019016014013011010033031026022019017015014012033033033033033031028025023033027022019016014013011010033031026022019017015014012033033033033033