Toa VM-3000 Series User Manual Page 124

  • Download
  • Add to my manuals
  • Print
  • Page
    / 149
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 123
124
VM-3240VA/3360VA rear
VM-3240VA/3360VA rear
Inside of the VM-3240VA/3360VA
How the surveillance function works under normal condition
How the surveillance function works under emergency condition
Inside of the VM-3240VA/3360VA
(Fire alarm or other control equipment)
24 V DC
-
+
24 V DC
+
-
Emergency control input
terminal 6
Control output terminals of the external device
(Fire alarm or other control equipment)
Control output terminals of the external device
Emergency control
input terminal 6
COM
Voltage
detector
The function judges the line
normal when 24 V DC is
detected at the emergency
control input terminal 6.
CTRL IN 6
COM
CTRL IN 6
COM
Emergency control
input terminal 6
COM
The function judges the line
normal when 24 V DC is
detected at the COM terminal.
Voltage
detector
Emergency control input
terminal 6
[Voltage control input terminal (EMERGENCY CONTROL 6)]
24 V DC is kept applied to the COM terminal under normal condition. Reversing this applied voltage polarity
activates an emergency broadcast.
The surveillance function judges the line normal when 24 V DC is detected at the COM terminal under
normal condition and when 24 V DC is detected at the emergency control input terminal 6 under emergency
condition.
It judges the line open if no voltage is detected under any condition.
The figures below show the line surveillance methods under normal and emergency conditions.
Page view 123
1 2 ... 119 120 121 122 123 124 125 126 127 128 129 ... 148 149

Comments to this Manuals